Fire Alarm Cable, FACS Series

Shielded, PVC CMR, PE, LSZH

Application

  • Widely used in indoor fire alarm, security alarm & Intercom system requiring flame retardancy properties.

Flame rating

  • NEC Article Type FPLR,CL3R, PVC CMR Rated comply to IEC 60332-1
  • LSZH IEC 60332-1
Construction
Conductor Grade A Bare Copper, Solid
Operating Voltage 300V
Insulation PVC
Insulation colour 1 – Black, 2 – Red, 3 – White, 4 – Green
1st Screen 100% Overall Aluminum Foil Screen
Sheath PVC-CMR or LSZH with Ripcord
Sheath colour PVC-CMR or LSZH RED
Rated temperature Up to 75°C
Cable Dimension
Conductor Size No of Pairs Nom. OD (mm)
12 AWG 1 Pair 6.5
2 Pairs 10.3
14 AWG 1 Pair 5.6
2 Pairs 8.9
16 AWG 1 Pair 4.8
2 Pairs 7.5
18 AWG 1 Pair 4.3
2 Pairs 6.7
Ordering Information
FACS 12-18 AWG part numbers are made up using the table below.
The part number starts with FACS to denote that it is a FACS cable.
Following number shows the number of pairing and the last 2 numbers signifies the AWG. 
Any letter behind would describe the sheath type & colour.

Example of a FACS part number-FACS1P18LRD
The above example describes an FACS cable with 1 pairing, 18 AWG. Sheath type LSZH with Red Jacket.

FACS PAIRING AWG SHEATH  Colour
FACS X XX X
1P – 1 Pair
2P – 2 Pairs
12 – 12 AWG
14 – 14 AWG
16 – 16 AWG
18 – 18 AWG
C – PVC-CMR
L- LSZH
RD- Red

Fire Alarm Cable, FACU Series

Unshielded, PVC CMR, PE, LSZH

Application

  • Widely used in indoor fire alarm or intercom system requiring flame retardancy properties.

Flame rating

  • NEC Article Type FPLR, CL3R, PVC CMR comply to IEC 60332-1
  • LSZH IEC 60332-1
Construction
Conductor Grade A Bare Copper, Solid
Operating Voltage 300V
Insulation PVC
Insulation colour 1 – Black, 2 – Red, 3 – White, 4 – Green
Ripcord Available
Sheath colour PVC-CMR or LSZH (Colour : RED)
Rated temperature Up to 75°C
Cable Dimension
Conductor Size No of Pairs OD (mm)
12 AWG 1 Pair 6.5
2 Pairs 10.3
14 AWG 1 Pair 5.6
2 Pairs 8.9
16 AWG 1 Pair 4.8
2 Pairs 7.5
18 AWG 1 Pair 4.3
2 Pairs 6.7
Ordering Information
FACU 12-18 AWG part numbers are made up using the table below.
The part number starts with FACU to denote that it is a FACU cable. 
The following number shows the number of pairs and the last 2 numbers signifies AWG. 
Any letter behind would describe the sheath type and sheath colour.

Example of a FACU part number-FACU2P12LRD
The above example describes an FACU cable with 2 pairing, 12 AWG. Sheath type PVC-CMR.

FACU PAIRING AWG SHEATH Colour
FACU X XX X X
1P – 1 Pair
2P – 2 Pairs
12 – 12 AWG
14 – 14 AWG
16 – 16 AWG
18 – 18 AWG
C – PVC-CMR
L- LSZH
RD-Red

Security & Comms Cable, SACS Series

Shielded, PVC CMR, PE, LSZH

Application

  • Security, Intercom, Broadcast, Sound, Audio Systems

Flame rating

  • PVC NEC Article Type FPLR, CL3R, CMR, comply to IEC 60332-1
  • LSZH IEC 60332-1
Construction
Conductor Grade A Bare Copper, Stranded
Operating Voltage 300V
Insulation PVC
Insulation colour 1 – Black, 2 – Red, 3 – White, 4 – Green
1st Screen 100% Overall Aluminum Foil Screen
Sheath PVC-CMR, PE or LSZH with Ripcord
Sheath colour PVC-CMR or LSZH Grey; PE Black
Rated temperature Up to 75°C
Cable Dimension
Conductor Size No of Pairs OD (mm)
12 AWG 1 Pair 7.6
2 Pairs 11.3
14 AWG 1 Pair 6.6
2 Pairs 9.7
16 AWG 1 Pair 5.2
2 Pairs 7.6
18 AWG 1 Pair 4.6
2 Pairs 6.6
20 AWG 1 Pair 4.2
2 Pairs 6.1
22 AWG 1 Pair 3.8
2 Pairs 5.3
Ordering Information
SACS Series part numbers are made up using the table below.
The part number starts with SACS to denote that it is a SACS cable.
The following number shows the number of pairs and the last 2 numbers signifies the AWG.
Any letter behind would describe the sheath type and colour.

Example of a SACS part number-SACS1P22LGY
The above example describes SACS cable with 1 pairing, 22 AWG. Sheath type LSZH.

SACS PAIRING AWG SHEATH Colour Drum Length
SACS X XX X X – X
1P – 1 Pair
2P – 2 Pairs
12 – 12 AWG
14 – 14 AWG
16 – 16 AWG
18 – 18 AWG
20 – 20 AWG
22 – 22 AWG
(nil) – PVC-CMR
E – PE
L- LSZH
GY-Grey -3H : 305m

Security & Comms Cable, SACU Series

Unshielded, PVC CMR, PE, LSZH

Application

  • Security, Intercom, Broadcast, Sound, Audio Systems

Flame rating

  • PVC NEC Article Type FPLR, CL3R, CMR, comply to IEC 60332-1
  • LSZH IEC 60332-1
Construction
Conductor Grade A Bare Copper, Stranded
Operating Voltage 300V
Insulation PVC
Insulation colour 1 – Black, 2 – Red, 3 – White, 4 – Green
Ripcord Available
Sheath colour PVC-CMR or LSZH Grey; PE Black
Rated temperature Up to 75°C
Cable Dimension
Conductor Size No of Pairs OD (mm)
12 AWG 1 Pair 7.5
2 Pairs 11.2
14 AWG 1 Pair 6.5
2 Pairs 9.6
16 AWG 1 Pair 5.1
2 Pairs 7.5
18 AWG 1 Pair 4.5
2 Pairs 6.5
20 AWG 1 Pair 4.1
2 Pairs 6.0
22 AWG 1 Pair 3.7
2 Pairs 5.2
Ordering Information
SACU Series part numbers are made up using the table below.

The part number starts with SACU to denote that it is a SACU cable.
The following number shows the number of pairs and the last 2 numbers signifies the AWG.
Any letter behind would describe the sheath type and jacket colour.

Example of a SACU part number-SACU1P16CGY 

The above example describes SACU cable with 2 pairs, 16 AWG. Sheath type PVC CMR with Grey jacket

SACU PAIRING AWG SHEATH  Colour
SACU X XX X X
1P – 1 Pair
2P – 2 Pairs
12 – 12 AWG
14 – 14 AWG
16 – 16 AWG
18 – 18 AWG
20 – 20 AWG
22 – 22 AWG
(nil) – PVC-CMR
E – PE
L- LSZH
GY-Grey

FIRETUF LTFIPNWM Fire Resistance SERIES

Heavy Armoured Cable Nylon + LSZH Sheath, Chemical/Corrosive Resistant

Features

  • Central Strength Member(CSM): glass fiber reinforced plastic rod(FRP), with PE coating when needed.
  • Tube: thermoplastic material containing up to 12 optical fibres and filled with a suitable water tightness compound.
  • Fire Resistance Layer: mica tape wrapped around loose tube
  • Stranding: The required numbers of elements (tubes or fillers) are SZ stranded around the central strength member.
  • Core Wrapping: water-blocking tape & yarn (dry-core)
  • Inner sheath: HDPE
  • Nylon sheath: Black Nylon Polyamide 12 (PA 12)
  • Outer Armour: Galvanized Steel Wire
  • Outer Sheath: LSZH flame retardant
Technical Data
No.of Flbres 4,8,16 12,24,36,48,72 96
Design (Elements x Fibre/Tube) 6×4 6 x 12 8×12
Loose Tube/Filler – ø mm Nom. 2.3 Nom. 2.0 Nom. 2.0
CSM/sheath diameter mm Nom. 3.0 Nom. 3.0 Nom. 3.0/4.8
Outer sheath thickness mm Nom. 2.0
Cable Diameter mm Nom. 17.9 Nom. 17.9 Nom. 19.7
Cable Weight Kg.Km 531 531 624
Max installation tension N 6000
Min. bending radius mm Without Tension
15 x Cable- ø
Under Maximum Tension
30 x Cable- ø
Temperature range Installation :
-10°C->+60°C
Transport & Storage :
-40°C->+70°C
Transport & Storage:
-40°C->+70°C

Application

The cable is specially designed for harsh environments. The multilayer inner sheath HDPE/PA(nylon) withstands aggressive constituents, fluids that might occur on (petro) chemical plants, aliphatic hydrocarbon resistant. The cable which is low smoke, halogen free and flame-retardant, is suitable for installation under and above ground. – Nylon jacket provides anti-termite protection of the cable
– The steel wire armour provides anti-rodent protection
– The outer sheath is flame retardant compound to Heat & Oil and UV resistant

Flame & Fire Rating

  • IEC 60332-3-24 & IEC 60331-25
Main Characteristics
Test Standard Specified value Acceptance Criteria*
Max. tension at installation (short term) IEC 60794-1-2-E1 5000N Δ I/I fibre strain ≤ 0.6%, Δα reversible
Crush IEC 60794-1-2-E3 4000N/100mm Δα ≤ 0.15dB(SM), 0.3 dB (MM) after test
Temperature Range IEC 60794-1-2-F1 -40 -> + 70ºC Δα ≤ 0.15dB/km(SM), 0.3 dB /km(MM)
Water penetration IEC 60794-1-2-F5C sample=3m, water=1m No water leakage after 24 hour

* Values for single-mode fibres, all optical measurements performed at 1550 nm
* Values for multi-mode fibres, all optical measurements performed at 1300 nm

Ordering Information
FIRETUF LTFIPNWM SERIES FO Cable part numbers are made up using the table below.

The part number always starts with the letters LTFIPNWM to denote that it is a FIRETUF LTFIPNWM SERIES FO Cable. 

This is followed by 3 numbers which symbolizes the core quantity and then 2 letters to denote the fibre type.

Example of a FIRETUF LTFIPNWM SERIES FO Cable part number: LTFIPNWM008M1

The above example describes an OM1 (62.5um, Black Sheath)

FIRETUF LTFIPNWM SERIES FO Cable, with 8 cores.

LTFIPNWM SERIES
Core quantity
FIBER TYPE
LTFIPNWM
XXX
XX
002~096 : (2 CORES ~ 96 CORES)
SM - SingleMode
M1~M4 - MultiMode

Category 3 UTP Multipair

U/UTP Data Cable

Application

These cables are used as riser cable in structured cabling networks, most often between distribution frames

Standards

  • IEC 61156, ISO/IEC 11801/1995, TIA/EIA 568 – A

Flame Rating

  • PVC IEC 60332 – 1,
  • LSZH IEC 60332-1
Construction
Conductor Solid bare copper wire, diameter 0.5 mm
Insulation Polyethylene, PE
Sheath PVC Black , also available on request with LSZH
Mechanical Properties
Minimum bending radius Without load 4 x OD ( OD= outer diameter )
With load 8 x OD ( OD= outer diameter )
Temperature During operation – 20° C to + 70° C
During operation    0° C to + 50° C
Electrical Properties
DC Resistance ≤ 117 Ω/ km
Insulation DC Resistance ≤ 5000 M Ω . km
Electrical Data at 20°C
Frequency Max.Attenuation Min. NEXT Min. ELFEXT Min. Return Loss   
(MHZ) (dB)  (dB) (dB) (dB)  
4 5.6 32.3 27.0 12.0
8 8.5 27.8 20.9 12.0
10 9.7 26.3 19.0 12.0
16 13.1 23.2 14.9 10.0
Ordering Information
P/N Product Description P.U  
ISV30250GY-5H Draka MMS Special Category 3 U/UTP  2 X 0.5mm PVC 500m/drum
ISV31050GY-5H Draka MMS Special Category 3 U/UTP  10 X 0.5mm PVC 500m/drum
ISV32050GY-5H Draka MMS Special Category 3 U/UTP  20 X 0.5mm PVC 500m/drum
ISV32550GY-5H Draka MMS Special Category 3 U/UTP  25 X 0.5mm PVC 500m/drum
ISV310050GY-5H Draka MMS Special Category 3 U/UTP  100 X 0.5mm PVC 500m/drum

LTFPNWM Flame Retardant SERIES

Heavy Armoured Cable Nylon + LSZH Sheath, Chemical/Corrosive Resistant

 

Application

  • The cable is specially designed for harsh environments. The multilayer inner sheath HDPE/PA(nylon) withstands aggressive constituents, fluids that might occur on (petro) chemical plants, aliphatic hydrocarbon resistant. The cable which is low smoke, halogen free and flame-retardant, is suitable for installation under and above ground. – Nylon jacket provides anti-termite protection of the cable
    – The steel wire armour provides anti-rodent protection
    – The outer sheath is flame retardant compound to Heat & Oil and UV resistant

Flame Rating

  • IEC 60332-3-22

Features

  • Central Strength Member(CSM): glass fiber reinforced plastic rod(FRP)
  • Tube: thermoplastic material containing up to 12 optical fibres and filled with a suitable water tightness compound.
  • Stranding: The required numbers of elements (tubes or fillers) are SZ stranded around the central strength member.
  • Core Wrapping: water-blocking tape & yarn (dry-core)
  • Inner sheath: HDPE
  • Nylon sheath: Black Nylon Polyamide 12 (PA 12)
  • Outer Armour: Galvanized Steel Wire
  • Outer Sheath: LSZH flame retardant
Configuration
No. of Flbers   4,8,12,24 32 36,48,72
Design (Elements x Fibre/Tube)   6×4 6×8 6×12
Loose Tube/Filler – ø mm Nom. 2.1 Nom.2.1 Nom. 2.1
CSM/sheath diameter mm Nom. 2.3 Nom. 2.3 Nom. 2.3
Outer sheath thickness mm Nom. 2.0
Cable Diameter mm Nom. 16.4 Nom.16.4 Nom. 16.4
Cable Weight kg.km 436 436 436
Max installation tension N 5000
Min. bending radius ( Without Tension) mm 15 x Cable ø
Min. bending radius ( Under Max. Tension)   25 x Cable ø
Main Mechanical and Environmental characteristics  
Test Standard Specified value Acceptance Criteria*  
Max. Tension IEC 60794-1-2-E1 See Configuration
Δ I/I fibre strain ≤ 0.6%,
Δα reversible
 
Crush IEC 60794 1-2-E3 4000 N/100 mm; reversible
Δα ≤ 0.15dB(SM), 0.3 dB (MM)
after test
 
Water penetration IEC 60794 1-2-F5C Sample=3m,water column=1m
No water leakages after 24hours
 
Temperature Range Transportation & Storage -40° C to +70 ° C  
Installation -10° C to + 70° C  
Operation -40° C to +70 ° C  
* Values for single-mode fibres, all optical measurements performed at 1550 nm
* Values for multi-mode fibres, all optical measurements performed at 1300 nm
 
Ordering Information
LTFPNWM SERIES FO Cable part numbers are made up using the table below.
The part number always starts with the letters LTFPNWM to denote that it is a LTFPNWM SERIES FO Cable.
This is followed by 3 numbers which symbolizes the core quantity and then 2 letters to denote the fibre type.
Example of a LTFPNWM SERIES FO
Cable part number: LTFPNWM008M1

The above example describes an OM1 (62.5um, Black Sheath) LTFPNWM SERIES FO Cable, with 8 cores.
 

 

LTFIPNWM SERIES Core Qty FIBRE TYPE  
LTFPNWM XXX
                XX
 
 
012-12 CORES
016-16 CORES
024-24 CORES
048-48 CORES
096-96 CORES

 

SM-SINGLEMODE, G652D, 9µm
M1-OM1, 62.5µm
M2-OM2, 50µm
M3-OM3, 50 µm
M4-OM4, 50µm
 
 

 

 

Draka Fire Resistant UC500 Cat.6a SFTP GSWB LSFRZH

Cat.6a 23AWG GSWB SFTP LSZH with circuit integrity behaviour

Application

  • Primary(Campus), Secondary(Riser), Tertiary(Horizontal)
  • IEEE 802.3: 10G Base-T
  • IEEE 802.5 16 MB; ISDN; TP DDI;ATM

Standards

  • ANSI/TIA-568.2-D
  • ISO/IEC 11801-1/2
  • IEC61156-5

Flame & Fire Rating

  • IEC 60331-23, IEC60332-1, IEC60332-3-24
Construction
Conductor Solid copper wire, (AWG 23)
Insulation Foam PE with special fire barrier tape
Twisting 2 cores to the pair
Screen Individual Pair Screen + Tinned Copper Braid Screen
Sheath LSZH with ATARUV
Tensile force 100 N
Mechanical Properties
Bending radius without load ≥ 16 x OD
with load ≥ 8 x OD
Temperature range during operation -15°C to + 60°C
during installation   0°C to + 50°C
Electrical Properties
DC Loop resistance ≤ 187.6 Ω/km
Impedance 1-100MHz  Nom. 100 Ω
DC Resistance unbalance ≤ 4%
Mutual capacitance at 1kHz ≤ 5.6 nF/100m
Ordering Information
P/N Product Description P.U
85048FRBRTVBK-3H  Draka UCDATA Category Cable UC500 CAT.6A SFTP 4 PAIR 23AWG GSWB LSFRZH FR ATARUV 305m/drum

MAX-FOH Flexible PAGA & Control Cable

Public Address General Alarm, Data Control Cable, Fire Resistance

Fire Characteristics
Conductor Grade A Copper specially protected by fire barrier tape to ensure circuit integrity in fire situations.
Construction Twisted pair for better signal transmission.
Core Insulation Cross-linked PE, XLPE
Outer Sheath LSZH in accordance to IEC 61034, IEC 60754-1 & 2.
Main Characteristics
Nominal overall diameter mm As per Technical Datasheet
Nominal weight (completed cable) Kg/km As per Technical Datasheet
Min bending radius mm As per Technical Datasheet
Max pulling tension kgf As per Technical Datasheet
Max conductor resistance @ 20°C Ω/km As per Technical Datasheet
Min insulation resistance @ 20°C MΩ/km As per Technical Datasheet
Dielectric withstand test kV/min As per Technical Datasheet
Technical Details
Size As per Technical Datasheet
Specification reference IEC 60332-1, IEC60332-3A, IEC 60331, BS
6387 CWZ
Conductor material mm Plain annealed copper wire to IEC
Max operating temperature °C 90
No of Wire / Wire Diameter mm As per Technical Datasheet
Conductor shape Circular stranded
Insulation Cross-linked PE, XLPE
Insulation thickness mm As per Technical Datasheet
Core Colour mm Black & White

Application

  • Most widely used fire resistance speaker & Audio/Motor control cables, which is highly flexible due to the unique tubing design. Draka MAX – FOH flexible speaker cables meets the stringent BS 6387 fire performance standards and can be used in all critical Public Address General Alarm Systems.

Fire Rating

  • Generally to :ISO/IEC 11801:95, IEC 61156, EN 50173:95; EN 50288-1,BS 6387
Ordering Information
P/N Product Description P.U
PAGA2C15 MAX-FOH FlexiTube, 2Cx1.5mm², PAGA Fire Res,

BS 6387, IEC 60331, LSZH, Orange

500m/drum
PAGA3C15 MAX-FOH FlexiTube, 3Cx1.5mm², PAGA Fire Res,

BS 6387, IEC 60331, LSZH, Orange

500m/drum
PAGA2C25 MAX-FOH FlexiTube, 2Cx2.5mm², PAGA Fire Res,

BS 6387, IEC 60331, LSZH, Orange

500m/drum
PAGA3C25 MAX-FOH FlexiTube, 3Cx2.5mm², PAGA Fire Res,

BS 6387, IEC 60331, LSZH, Orange

500m/drum

Draka Style 2919

Individual Pair Screened Control Cable

Application

  • For installation require flexible cable to fulfill measuring, controls & command applications. Example Computer Interconnection, Data Transmission, Control Circuits, Industrial Equipment Control, suitable for RS-485 applications.

Optional

  • PVC/Steel Wire Braid
  • High pair counts upon request.
Technical Details
Conductor Stranded Tinned Copper
Operating Voltage 300V
Insulation HD-PE/Foam-PE
Insulation colour Pair 1: White*Orange
1st screen 1 x AL-Mylar Wrap, overlapping >= 25 %
Drain wire 7/0.254mm Stranded Tinned Copper
Braid Shielding Tinned Copper Braid
Sheath LSZH
Sheath Colour Grey
Operating Temperature -20°C ~ +70°C
Cable Dimension
Conductor Size DC Resistance @ 20°C (Ω/km) No of Pairs Nom. OD (mm)
18 AWG <= 23.2 1 Pair 7.5
<= 23.2 2 Pairs 10.3
<= 23.2 4 Pairs 12.8
20 AWG <= 36.7 1 Pair 7.0
<= 36.7 2 Pairs 9.3
<= 36.7 4 Pairs 11.5
22 AWG <= 58.0 1 Pair 6.5
<= 58.0 2 Pairs 9.8
<= 58.0 4 Pairs 11.5
24 AWG <= 89.0 1 Pair 6.5
<= 89.0 2 Pairs 9.0
<= 89.0 4 Pairs 10.2
Ordering Information
Draka Style 2919 part numbers are made up using the table below.
The part number starts with 29 to denote that it is a UL 2919 cable.
The following number shows the number of pairing and the last 2 numbers signifies the AWG.
Any letter behind would describe the sheath & colour type.

Example of a Draka Style 2919 part number : 29418LGY




The above example describes an UL 2919 cable with 4 pairing, 18 AWG. Sheath type LSZH.

UL 2919 PAIRING AWG SHEATH  Colour
29 X XX X X
1 - 1 Pair
2 - 2 Pair
3 - 3 Pair
4 - 4 Pair
18 - 18 AWG
20 - 20 AWG
22 - 22 AWG
24 - 24 AWG
(nil) - PVC
L- LSZH
GY - GREY
BK- BLACK