ICS IE ToughCat 7 LSHF-FR

S/FTP Installation Cable 4x2xAWG23/7 for tougher environments

Construction
Conductor Stranded copper wire, cross section 0.27 mm² (AWG23/7)
Insulation PE
Twisting 2 cores to the pair
Cable lay up 4 pairs
Pair screen Al-laminated plastic foil around each pair
Overall screen Tinned Copper Braid
Sheath Oil resistant, Fire retardant and halogen free LSZH-FR (SHF1), diameter 8.1 mm
Colour Grey RAL 7035
Outer Diameter Nom. 8.1 mm
Weight Nom. 75 kg/km
Tensile force N 100
Mechanical properties
Bending radius Without load 8 x D
With load 4 x D
Temperature range During operation -40°C to + 85°C
During installation -15°C to + 50°C
Fire load 4 pair 670 MJ/km
Maximum tensile load During operation No load
During installation 140 N
Electrical properties at 20°C
DC Loop resistance ≤ 138 Ω/km
Resistance unbalance ≤ 2%
Mean Characteristic impedance @ 100 MHz 100 Ω± 5 Ω
Nominal velocity of propagation 76%

Application

  • Generic Data transmission. This cable is a Cat7 S/FTP cable meant for use as installation/horizontal cable in tougher electrical and mechanical environment, including ships and offshore units.

Standards

  • EN50173-1,EN50288-4-1
  • ISO/IEC 11801,IEC61156-5
  • Det Norske Veritas(DNV) specification No. 6-827.50-2

Flame Rating

  • IEC 60332 – 1 , IEC 60332-3-24, IEC -61034-2, IEC 60754 – 1 /2

Chemical Resistance

  • Mineral oils IRM902(IEC 60811-2-1)
  • Diesel – IRM 903(IEC60811-2-1)

Certification

  • This cable is certified by :Det Norske Veritas(DNV) and American Bureau of Shipping(ABS)
Electrical Transmission Characteristics at 20°C
Freq. Attenuation NEXT ACR Return loss PS-NEXT
(MHZ) (dB/100m) (dB) (dB/100m) (dB) (dB)
1 2.0 90 88 87
4 3.6 90 86 27 87
10 5.5 90 84 30 87
16 7.5 90 82 30 87
20 7.7 90 82 30 87
31.25 9.8 90 80 30 87
62.50 14.0 86 72 30 83
100 17.9 83 65 30 80
155 22.4 81 59 26 78
200 25.6 78 52 25 75
250 28.8 77 48 25 74
300 31.6 73 41 23 70
600 45.7 71 25 20 68
Ordering Information
P/N Product Description P.U
60015820 ToughCat C7 LSHF-FR 4×2/0.27mm2 500m/drum
60030363 ToughCat C7 LSHF-FR 4×2/0.27mm2 1000m/drum

ICS IE ToughCat 5e LSHF-FR

S/FTP Installation Cable 4x2xAWG24/7 for tougher environments

Construction
Conductor Stranded copper wire, cross section 0.22 mm² (AWG24/7)
Insulation PE
Twisting 2 cores to the pair
Cable lay up 4 pairs
Pair screen Al-laminated plastic foil around each pair
Overall screen Copper braid, tinned
Sheath Oil resistant, Flame retardant and halogen free LSZH-FR (SHF1)
Colour Grey RAL 7035
Outer Diameter Nom. 7.7 mm
Weight Nom. 68 kg/km
Tensile force N 100
Mechanical properties
Bending radius Without load 8 x D
With load 4 x D
Temperature range During operation -40°C to + 85°C
During installation -15°C to + 50°C
Fire load 4 pair 670 MJ/km
Maximum tensile load During operation No load
During installation 100 N
Electrical properties at 20°C
DC Loop resistance ≤ 158 Ω/km
Resistance unbalance ≤ 2%
Insulation resistance (500 V) ≥ 5000 MΩxkm
Capacitance at 800 Hz Nom. 43 nF/km
Mean Characteristic impedance @ 100 MHz 100 Ω± 5 Ω
Nominal velocity of propagation 75%

Application

  • Generic Data transmission. This cable is a Cat5e S/FTP cable is meant for use as installation/horizontal cable in tougher electrical and mechanical environment,including ships and offshore units.

Standards

  • EN 50288-2-1
  • Det Norske Veritas(DNV GL) Class Program DNVGL-CP-0403 and Lloyd Register approval system 2002

Flame Rating

  • IEC 60332 – 1, IEC 60332-3-24

Chemical Resistance

  • Mineral oils IRM902(IEC 60811-2-1)
  • Diesel – IRM 903(IEC60811-2-1)

Certification

  • This cable is certified by :Det Norske Veritas(DNV) and Llyod Register
Electrical Data Nominal at 20°C
Freq. Attenuation NEXT ACR Return loss PS-NEXT PS-ACR ELFEXT PS-ELFEXT
(MHZ) (dB/100m) (dB) (dB/100m) (dB) (dB) (dB/100m) (dB/100m) (dB/100m)
1 2.1 90 88 87 85 85 82
4 4.0 90 86 27 87 83 85 82
10 6.3 90 84 30 87 81 79 76
16 8.0 90 82 30 87 79 75 72
20 9.0 90 81 30 87 78 73 70
31.25 11.4 90 79 30 87 76 69 66
62.50 16.50 86 70 30 83 67 63 60
100 21.3 83 62 30 80 59 59 56
Ordering Information
P/N Product Description P.U
60015830 ToughCat C5e LSHF-FR 4×2/0.22mm² 500DP 500m/drum
60015833 ToughCat C5e LSHF-FR 4×2/0.22mm² 1000DP 1000m/drum

Draka UC400 Cat.6 U/FTP 23AWG LSFRZH AR_AT_UV

Category cable for demanding environments

Application

  • Generic Data transmission. This cable is a Cat6 U/FTP cable is meant for use as installation/horizontal cable in demanding electrical and mechanical environment.

Standards

  • ANSI/TIA 568.2-D;
  • ISO/IEC 11801-1/2; IEC 61156 – 5
  • EN 50173; EN 50288-5-1

Flame Rating

  • IEC 60332-1, IEC 60332-3-24
Construction
Conductor Solid copper wire, (AWG23)
Insulation Foam PE
Twisting 2 cores to the pair
Pair Screen Individual Aluminium Foil Polyester Tape with drain wire
Outer Sheath LSFRZH. AR-AT-UV
Sheath Colour Black
Mechanical properties
Bending radius Installation 8 X D
Temperature range During operation -20°C to + 70°C
During installation 0°C to + 50°C
Maximum Pulling Force  During installation 100N
Electrical properties at 20°C
DC Loop resistance ≤ 187.6 Ω/km
DC Resistance unbalance ≤ 5%
Mutual capacitance at 1kHz ≤ 5.6nF/100m
Capacitance unbalance (pair/ground) ≤ 536 ns/100m
Velocity of Propagation Nom. 69%
Electrical Data at 20°C
Freq. Max. Attenuation Min.NEXT Min.PS-NEXT Min.Return Loss
(MHZ) (dB/100m) (dB) (dB) (dB)
1 2.0 74.3 72.3 20.0
4 3.8 65.3 63.3 23.0
16 7.6 56.2 54.2 25.0
25 9.5 53.3 51.3 24.3
62.5 15.4 47.7 45.7 21.5
100 19.8 44.3 42.3 20.1
200 29.0 39.8 37.8 18.0
250 32.8 38.3 36.3 17.3
Ordering Information
P/N Product Description P.U
66048RTVBK-5H Draka UCDATA CATEGORY CABLE UC400 CAT.6 UFTP 4 PAIR 23AWG LSFRZH ATARUV BLACK IEC60332-3-24, IEC60754-1&2, IEC 61034 500m/drum

Draka UC500 Cat.6a S/FTP SWB LSZH AR_AT_UV

Category cable for demanding environments

Construction
Conductor Solid copper wire (AWG23)
Insulation Foam PE
Twisting 2 cores to the pair
Pair Screen High Performance Individual Pair Screen
Overall screen Tinned Copper Braid
Inner Sheath LSZH
Armouring Galvanized Steel Wire Braid
Outer sheath LSZH (AR-AT-UV)
Sheath colour Black
Mechanical properties
Bending radius Installation (No Load) 8 x D
Temperature range During operation -20°C to + 70°C
During installation  0°C to + 50°C
Electrical properties at 20°C
DC Loop resistance ≤ 187.6Ω/km
DC Resistance Unbalance ≤ 4%
Characteristic impedance 1-100Mhz 100 ± 15 Ω
Mutual capacitance at 1kHz ≤ 5.6nF/100m
Capacitance unbalance (pair to ground) ≤ 300 pF/100m
Nom. Velocity of Propagation 76%

Application

  • Generic Data transmission. This cable is a Cat6a S/FTP cable is meant for use as installation/horizontal cable in demanding electrical and mechanical environment.
  • Suitable for installation in Anti-Termite, Anti-Rodent & UV Resistance area.

Standards

  • ANSI/TIA 568.2-D;
  • ISO/IEC 11801-1/2 ; IEC 61156 – 5
  • EN 50173; EN 50288- 5 -1

Flame Rating

  • IEC 60332 – 1
Electrical Data Nominal at 20°C
Freq. Max. Attenuation Min. Return loss Min. NEXT
(MHZ) (dB) (dB) (dB)
1 2.1 20 74.3
4 3.8 23 65.3
16 7.5 25 56.2
100 19.1 20.1 44.3
250 31.1 17.3 38.3
500 45.3 15.2 33.8
Ordering Information
P/N Product Description P.U
85075BRTVBK-5H Draka UCDATA CATEGORY CABLE UC500 CAT.6A SFTP 4 PAIR 23AWG GSWB Armoring LSZH ATARUV Black IEC60332-1, IEC 60754-1&2, IEC 61034 500m/drum

PB DP FC 1x2xAWG22/7 SWB LSHF

PROFIBUS DP FC Steel Wire Braid Armoured LSHF Cable, 150 Ohm

Application

Armoured indoor and outdoor Installation cable:

– Halogen free and flame retardant

– Limited segment length (according to PROFIBUS – Net Manual)

– FastConnect-assembly

– UV resistant

– Silicon free

– Limited oil and grease resistance

Standards

  • EN 50170 part 8-2, cable type A, IEC 61158 and IEC 61784

Flame Rating

  • IEC 60332-1, IEC 60332-3-24
Construction
Conductor Stranded bare copper wire, ∅ 0.78 mm, (cross-section 0.37 mm²)
Insulation foam-skin-PE, Ø 2.55 mm
Stranding two cores green / red to the Pair
Bedding halogen free, flame retardant thermoplastic sheathing compound
Static screen PET-Al-Foil longitudinally applied
Braid tinned copper braid, coverage approx. 65%
Sheath halogen free, flame retardant thermoplastic sheathing compound acc. to
Armouring Galvanized Steel Wire Braid
Outer sheath halogen free, flame retardant thermoplastic sheathing compound
Outer Diameter Nom. 12.0 mm
Weight Nom. 208 kg/km
Tensile force N 450
Mechanical properties
Bending radius
Single bending ≥ 120 mm
Repeated bending ≥ 240 mm
Temperature range – 10°C to + 75°C
Transport and storage – 10°C to + 75°C
Installation – 5°C to + 50°C
Electrical properties at 20°C
Loop resistance ≤ 110 Ω
Characteristic impedance (Nominal) 150 Ω ± 20Ω
Mutual capacitance (at 1 kHz) approx. 28.5 nF/km
Capacitance unbalance to earth max. 1.5 nF/km
Test Voltage (DC, 1 min) Core/Core and Core/Screen 1 kV
Electrical Data at 20°C
Frequency (kHz) Impedance (Ohm) Attenuation (dB/100m)
9.6 kHz 270 ± 27 ≤ 0.3
38.4 kHz 185 ± 18.5 ≤ 0.4
1 MHz
3 MHz 150 ± 15
4 MHz 150 ± 15 ≤ 2.5
16 MHz 150 ± 15 ≤ 4.9
20 MHz 150 ± 15
Ordering Information
P/N Product Description P.U
TBC PROFIBUS DP FC Steel Wire Braid Armoured LSHF Cable, PB DP FC 1x2xAWG22/7 SWB LSHF 1000m/drum

PB DP FC 1x2xAWG22/1 LSHF-FR

PROFIBUS FC LSHF-FR Cable, 150 Ohm

Construction
Conductor Solid Bare Copper Wire, ∅ 0.64 mm, (cross-section 0.32 mm²)
Insulation foam-skin-PE, ∅ 2.5 mm
Stranding two cores green / red to the Pair
Bedding halogen free, flame retardant thermoplastic sheathing compound
Static screen PET-Al-Foil longitudinally applied
Braid tinned copper braid, coverage approx. 60%
Sheath halogen free, flame retardant thermoplastic sheathing compound
Outer Diameter Nom. 8.0 mm
Weight Nom. 83 kg/km
Tensile force N 800
Mechanical properties
Bending radius
Single bending ≥ 60 mm
Repeated bending ≥  80 mm
Temperature range – 15°C to + 70°C
Transport and storage – 15°C to + 70°C
Installation – 15°C to + 50°C
Electrical properties at 20°C
Loop resistance ≤110 Ω/km
Screen resistance nominal ≤ 9.5 Ω/km
Characteristic impedance (Nominal) 150 Ω
Mutual capacitance (at 1 kHz) ca. 28.5 nF/km
Test Voltage (DC, 1 min) Core/Core and Core/Screen 1 kV
Operating voltage (RMS) ≤ 100 V

Application

Installation cable:

– Halogen free and flame retardant

– Limited segment length (according to PROFIBUS – Net Manual)

– Fast Connect-assembly

– UV resistant

– Silicon free

– Limited oil and grease resistance

Flame Rating

  • IEC 60332 – 1, IEC 60332-3-24
Electrical Data at 20°C
Frequency (kHz) Impedance (Ohm) Attenuation (dB/100m)
9.6 kHz 270 ± 27 ≤ 0.25
38.4 kHz 185 ± 18.5 ≤  0.4
1 MHz
3 MHz 150 ± 15
4 MHz 150 ± 15 ≤  2.2
16 MHz 150 ± 15 ≤  4.2
20 MHz 150 ± 15
Ordering Information
P/N Product Description P.U
60011470 PROFIBUS FC LSHF-FR Cable, ICSPB DP FC 1x2xAWG22/1 LSHF-FR 1000m/drum

PB DP BASIC 1x2xAWG22/1 LSHF

PROFIBUS DP Basic LSZH Cable,150 Ohm

Application

Installation cable:

– Halogen free and flame retardant

– Limited segment length (according to PROFIBUS – Net Manual)

– UV resistant

Standards

  • IEC 61158-2

Fire Rating

  • IEC 60332 -3-24
Construction
Conductor Solid Bare Copper Wire, 22AWG
Insulation Foam-skin-PE
Stranding two cores green / red to the pair and two fillers
Static screen PET-Al-Foil longitudinally applied
Braid Tinned Copper Braid
Sheath Low Smoke Zero Halogen compound
Violet RAL 4001
Outer Diameter Nom. 7.8 mm
Weight Nom. 71 kg/km
Mechanical properties
Bending radius ≥ 60mm
Max. operating voltage – 40°C to + 80°C
Electrical properties at 20°C
Conductor resistance ≤ 55Ω/km
Characteristic impedance (Nominal) 150 Ω
Mutual capacitance (at 1 kHz) ca. 28.5 nF/km
Test Voltage (DC, 1 min) Core/Core and Core/Screen 1 kV
Operating voltage (RMS) 300 V
Ordering Information
P/N Product Description P.U
PDP122FLVVL-5H PROFIBUS DP Data Communication Cable Cable, BC/FPE/OS/TCB/LSZH UV 1PR x 22AWG VIOLET 500m/drum

FF FC 1x2xAWG18/7 SWB LSZH

FOUNDATION Fieldbus FC FLEX Steel Wire Braid Armoured LSZH Cable

Construction
Conductor stranded bare copper wires, 7×0.40, ø 1.2 mm, (cross-section AWG18/7)
Insulation foam-skin-PE, ø 2.55 mm
Stranding two cores blue / orange to the pair
Bedding LSHF, filling the interstices.
Static screen PET-Al-Foil longitudinally applied.
Braid tinned copper braid, coverage approx. 70%
Sheath LSZH, ø 8.0 mm
Colour Grey
Armouring galvanized steel wire braid, optical coverage 85%, ø 9.3 mm
Outer sheath LSZH, ø12.0 mm
Colour Grey
Outer Diameter Nom. 12.0 mm
Weight Nom. 202 kg/km
Tensile force N 500
Mechanical properties
Bending radius
Single bending ≥ 60 mm
Repeated bending ≥ 120 mm
Temperature range – 30°C to + 70°C
Transport and storage – 30°C to + 70°C
Installation – 5°C to + 50°C
Electrical properties at 20°C
Loop resistance ≤ 43.6 Ω/km
Screen resistance nominal 12 Ω/km
Characteristic impedance (at 31.25 kHz) 100Ω ± 20 Ω
Mutual capacitance (at 1 kHz) approx. 60 nF/km
Capacitance unbalance to earth max. 2 nF/km
Test Voltage (DC, 1 min) Core/Core and Core/Screen 1 kV
Operating voltage (RMS) ≤ 100 V
Inductance (nominal) 0.70 mH/km

Application

Spur and trunk cable for flexible installation indoor and outdoor on racks in conduits,

– Fast connect Assembly

– Halogen free and flame resistant

– Silicon free

– Oil and grease resistance

Standards

  • IEC 61158 and IEC 61784
  • Cable Type A acc. to FOUNDATION Fieldbus

Fire Rating

  • IEC 60332-1, IEC 61034 – 2, IEC 60754 – 1 / 2
Electrical Data at 20°C
Frequency (kHz) Impedance (Ohm) Attenuation (dB/100m) Propagation delay change (µs/km)
7.9-39 ≤ 1.7
31.25 100 ± 20
39 ≤ 0.3
Ordering Information
P/N Product Description P.U
1030290 FOUNDATION Fieldbus FC FLEX Steel Wire Braid Armoured LSZH Cable,FF FC 1x2xAWG18/7 SWB LSZH 1000m/drum

FF FC 1x2xAWG18/7 LSHF-FR

FOUNDATION Fieldbus FC FLEX LSZH-FR Cable

Application

Spur and trunk cable for flexible installation indoor and outdoor on racks in conduits, Fast connect Assembly

– UV resistant

– Silicon free

– Oil and grease resistant

Standards

  • IEC 61158 and IEC 61784
  • Cable Type A acc. to FOUNDATION Fieldbus

Fire Rating

IEC 60332-1, IEC 60332-3-24, IEC 60754-1/2

Construction
Conductor Stranded bare copper wires, 7×0.40, ∅ 1.2 mm, (cross-section AWG18/7)
Insulation foam-skin-PE, ∅ 2.55 mm
Stranding two cores green / red to the Pair
Bedding halogen free, flame-retardant thermoplastic sheathing compound
acc. to EN 50290-2-27, filling the interstices.
Static screen PET-Al-Foil longitudinally applied.
Braid tinned copper braid, coverage approx. 70%
Sheath halogen free, flame-retardant thermoplastic sheathing compound
acc. to EN 50290-2-27, 0 8.0 mm
Colour yellow
Outer Diameter Nom. 8.0 mm
Weight Nom. 83 kg/km
Tensile force N 180
Mechanical properties
Bending radius
Single bending ≥ 40 mm
Repeated bending ≥ 80 mm
Temperature range – 40°C to + 70°C
Transport and storage – 40°C to + 70°C
Installation – 5°C to + 50°C
Electrical properties at 20°C
Loop resistance ≤ 43.6 Ω/km
Screen resistance nominal 12 Ω/km
Characteristic impedance (at 31.25 kHz) 100 Ω ± 20 Ω
Mutual capacitance (at 1 kHz) approx. 60 nF/km
Capacitance unbalance to earth max. 2 nF/km
Insulation resistance ≥ 5 GΩkm
Test Voltage (DC, 1 min) Core/Core and Core/Screen 1 kV
Operating voltage (RMS) ≤ 100 V
Inductance (nominal) 0.70 mH/km
Electrical Data at 20°C
Frequency (kHz) Impedance (Ohm) Attenuation (dB/100m) Propagation delay change (µs/km)
7.9-39 ≤ 1.7
31.25 100 ± 20
39 ≤ 0.3
Ordering Information
P/N Product Description P.U
1025038 FOUNDATION Fieldbus FC FLEX LSHF-FR Cable, FF FC 1x2xAWG18/7 LSZH-FR 1000m/drum

Li-2YC11Y 2 x 2 x 0.22 mm² FRNC

CanBus-Cable

Application

  • The following CanBus cable is suitable for transmission of CanBus signals according to DIN19245 and EN 50170
  • The following CanBus cable is suitable for transmission of CanBus signals according to ISO 11898 – 2
  • The cable is suited for fixed indoor and outdoor installation and under certain conditions also for mobile use.
  • The cable is halogen free,flame retardant and oil resistant. The sheath material is tested in Hydraulic oil.
  • ARAL VITAM 32, Mobil DTE 13 M, Gear oil ARAL DEGOL BG Plus 320 and Tribol 1710/320

Flame resistance

  • IEC 60332 – 1,IEC -60332-3,IEC 60754 – 1 /2
Construction
Conductor Stranded bare copper wire, diameter 7 x 0.20 mm            
ø 0.60 mm(cross section 0.22 mm²)
Insulation PE,
ø1.75± 0.05 mm
Wall Thickness 0.46mm
Colour code Pair 1: 1 x white, 1 x brown
Core identification Pair 2: 1 x yellow, 1 x green
Cable lay up 4 cores twisted to a star quad
ø 4.2 mm
Wrapping 1 x PET-foil, overlapping
ø 4.3 mm
Overall screen Tinned copper braid
ø 5.0 mm, Optical coverage ≥ 85%
Foil 1 x PET-foil under sheath
ø 5.1 mm
Sheath PUR Low Smoke Zero Halogen
ø 6.9 ± 0.2 mm
Sheath colour Black, RAL 9005
Outer Diameter Nom. 6.9 mm
Weight Nom. 70 kg/km
Tensile force N 165
Mechanical properties
Bending radius
– moving application- fixed application
≥ 10 x outer diameter of cable

≥ 5 x outer diameter of cable

Operating temperature – 40°C up to + 85°C
UV resistance acc. to IEC60068-2-5
Ozone resistance acc. to EN 60811-2-1, clause 8
Smoke density acc. to EN 50268-2, IEC61034-1 and 2
Corrosivity EN 50267-1 and 2, IEC 60754-1 and 2
Electrical properties at 20°C
Conductor resistance (at 20 ± 5 °C) ≥ 87 /km
Characteristic impedance at 1 MHz 120 Ω± 15%
Capacitance at 800 Hz (nominal) 41 nF/kmm
Insulation resistance (at 20 ± 5 °C and 500 V) ≥10 GΩxkm
Capacitance unbalance (pair to ground) 1.2 kV
Ordering Information
P/N Product Description P.U
1003018 CS2878600 CanBus, Li-2YC11Y 2 x 2 x 0.22 mm² FRNC 1000m/drum