LONAK® 2x2x0.8

Building automation cable

Construction
Conductor Copper wire, tinned 0.5 mm2 , Ø 0.80 mm
Insulation PVC, 1.6 mm Ø
Conductor identification Pair 1: white-blue, blue, Pair 2: white-orange, orange
Stranding 4 conductors to the quad
Cable lay up 1 pair to the core
Wrapping 1 x PET foil
Overall shielding Laminated AL-foil + copper drain wire
Rip cord and identification thread yes
Outer sheath PVC, grey RAL 7035, Ø 7.0 mm
Outer Diameter Nom. 7.0 mm
Weight Nom. 54 kg/km
Mechanical properties
Operating temperature - 30°C to + 70°C
Min. Installation temperature - 5°C
Minimum bending radius 10 x D
Minimum bending radius (during pulling) 15 x D
Maximum pulling force 100 N
Electrical properties at 20°C
Loop DC resistance (max.) 73 Ω/km
Insulation resistance (at 500 V, 1 min.) 100 MΩ*km
Mutual capacitance at 800 Hz (max.) 98 nF/km
Velocity factor 0.55
Max. operating voltage DC 75 V
Test voltage conductor/conductor 2.25 kV DC, 1 min.
Test voltage conductor/screen 1.5 kV DC, 1 min.

Application

  • Fixed indoor installations
  • LON cabling
  • Building automation

Fire Rating

  • IEC 60332-1
Ordering Information
P/N Product Description P.U
1003580 CS2638200 L432498 2x2x0.8 mm, Building automation cable, LONAK® 2x2x0.8 1000m/drum